Fluke 1507-NIST Insulation Resistance Tester, 50 to 1000 V

1507-NIST.webp

Part Number : 1507-NIST

Brand : Fluke

Ideal for electrical contractors and industrial and commercial electricians, this insulation resistance tester also comes in a compact and rugged design and is easy to use. Additionally, this tool is great for troubleshooting, commissioning, and preventative maintenance applications. This product includes a Traceable Certificate with full Data and Uncertainties.

View all

$ 991.99


Quantity In Stock



Description
Specifications
Downloads
Related products

Description

Fluke 1507-NIST Offers Ideal for advanced industrial and electrical insulation testing, this insulation tester comes in a compact design and features versatility. Additionally, the multiple test voltages facilitate the tool for many troubleshooting, commissioning, and preventative maintenance applications. Take advantage of the full feature set to easily and quickly perform advanced insulation resistance testing. Its handy size and lightweight make it easy to pack and use. Additional features, like the remote probe, save both time and money, especially when performing repetitive tests. This product includes a Traceable Certificate with full Data and Uncertainties. Features Rugged, compact advanced insulation resistance tester for electrical contractors and industrial and commercial electricians Automatically calculates polarization index and dielectric absorption ratio Makes repetitive tests simple and easy with a compare (pass/fail) function Offers multiple insulation test voltages: 50, 100, 250, 500, and 1000 V Performs insulation tests from 0.01 M? to 2.0 G? Includes live circuit detection to prevent insulation test if voltage >30 V is detected Includes auto-discharge of capacitive voltage for added user protection Measures AC/DC voltage from 0.1 to 600 V and resistance from 0.01 ? to 20.00 k? Provides lo-ohms earth-bond continuity (200 mA) Simplifies repetitive or hard-to-reach testing with the remote test probe Saves battery power with auto power off Presents results on a large, backlit display Features CAT IV 600 V over voltage category rating Runs on four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests Applications Troubleshooting Commissioning Preventative maintenance 6 Tips for effective insulation testing 1 Disconnect any electronic devices like motor drives, PLC’s, transmitters, etc. before performing insulation testing. Electronics can be damaged by applying higher than normal voltage. 2 The effect of temperature should be considered - it is recommended that tests be performed at a standard conductor temperature of 20 °C (68 °F) or that a temperature baseline is established while compensating future readings by using a DMM with a probe or an infrared thermometer. 3 Select a test voltage appropriate for the insulation being tested. The objective is to stress the insulation but not to over-stress it. When in doubt, use a lower test voltage. It’s usually appropriate to test insulation at twice the voltage it normally sees: for example 460 V to 600 V rated equipment is often tested at 1000 V. 4 When using an insulation tester, leave the leads connected when you stop the test. The insulation tester can discharge any residual test voltage. 5 Conductors that are close to each other have a normal capacitance. This will cause an insulation resistance reading to start low and increase steadily until it stabilizes. This type of increase is normal, but if the reading jumps violently down and up again this indicates arcing. 6 Although the current is tightly limited, an insulation tester can generate sparks and minor but painful burns. The unexpected surprise can cause an operator to jerk away. As always, work away from live systems and use safe work practices when working overhead. Insulation Resistance Testing Solutions

Downloads

1507-NIST.pdf

pdf

Specifications

Range
  • 600.0 V
  • 20.00 Ω to 20.00 kΩ
Resolution
  • 0.1 V
  • 0.01 Ω to 0.01 kΩ
Accuracy
  • 50 Hz to 400 Hz: ±(2% of rdg + 3 digits)
  • ±(1.5% + 3 digits)
Input Impedance
3 MΩ (nominal), < 100 pF
Common Mode Rejection Ratio (1 kΩ unbalanced)
>60 dB at DC, 50 or 60 Hz
Overload Protection
  • 600 V RMS or DC
  • 2 V RMS or DC
Open Circuit Test Voltage
>4.0 V, <8 V
Short Circuit Current
  • >200.0 mA
  • 1 mA nominal
Measurement Range
0.01 MΩ to 10 GΩ
Test Voltage
50, 100, 250, 500, 1000 V
Test Voltage Accuracy
+20%, -0%
Auto Discharge
Discharge time <0.5 second for C = 1 µF or less
Live Circuit Indicator
Inhibit test if terminal voltage >30 V prior to initialization of test
Maximum Capacitive Load
Operable with up to 1 µF load
Live Circuit Detection
Inhibit test if terminal voltage > 30 V prior to initialization of test
Measure Accuracy
50 V: ±(3% + 5) 100 V: ±(3% + 5) 250 V: ±(3% + 5) 500 V: ±(3% + 5) 1000 V: ±(3% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ
Industrial Spare Logo

Industrial Spare
Typically replies within an hour

Industrial Spare
Hi there,

How can I help you?
+96566651231
×
Chat with Us