The New ULTRAFLO U1000MKII-HM-WM is a Clamp-on, Ultrasonic heat/energy meter with a separate wall mounted keypad and display, a “Best Value” alternative to traditional inline energy meters, for energy management and billing applications in domestic and commercial, district or shared heating or cooling systems. Offering significant installation cost and dry maintenance benefits over traditional inline products.

Key Features & Benefits

• Clamp-on pipe mounted sensors with Wall Mounted keypad and display for wall or panel mounting • larger pipe range Available in 2 options. 22mm – 115mm OD and 125mm – 225mm OD • Optional Modbus RTU slave, RS485 serial and M-Bus communication. • Ultrasonic, cross-correlation transit time method for flow measurement. • 1Mhz transducers to get through poor/old thick wall pipes and larger pipework • Water/Glycol option • Simple to install: connect power and enter the pipe inside diameter, adjust the sensors and clamp-on the pipe, no specialist skills or tools required • A clamp-on non-invasive alternative heat/energy meter to traditional in-line meter installation, plus dry servicing, providing minimum downtime and maximum availability. • LCD with backlight – install & service information. • Integrated pulse output for Volume flow and Energy in kWh(BTU). – aM&T & BEM’s compatible with Modbus.

Downloads

U1000MKII-WM HM.pdf

pdf

U1000MKII HM Manual.pdf

pdf

U1000MKII range.pdf

pdf

Specifications

Measurement Technique
Ultrasonic, cross-correlation transit time method for flow measurement.
Turn Down Ratio
100:1
Heat Meter Standard
The Heat/Energy calculation is designed to comply with EN1434 section 6
Accuracy
±1% -3% of flow reading for velocity rate >0.3 m/s (>1 ft/s)
Flow Velocity Range
0.1 m/s – 10 m/s (0.3 ft/s – 32 ft/s)
Pipe Range
Available in 2 options, 25 mm – 115 mm OD and 125 mm – 225 mm OD. Note pipe size is dependent on pipe material and internal diameter.
Pipe Material
Steel, Stainless Steel, Plastic and Copper
Water Temp Range
0°C – 135°C (32°F – 275°F)
Option
Additional 4-20mA output option for flow only, which can be purchased / used at the same time as modbus / mbus.
Temperature sensors
Clamp-on PT100 Class B 4 wire, range 0°C – 135°C (32°F – 275°F), resolution 0.1°C (0.18°F). Minimum delta T is 0.3°C
Pulse Output
Pulse or Frequency. Pulse for volume flow and Energy in kWh (BTU). Frequency for flow rate. The pulse output can be configured as a loss of signal or low flow alarm. Opto-isolated MOSFET volt free contact [NO/NC].
Modbus Communication
Optional Modbus RTU slave, RS485 serial link hardware layer. Energy, power, temperature and flow.
M-Bus Communication
Optional.
External Power Supply
12V-24V ±10% AC/DC at 7 watts per unit. Optional plug in 12V power supply.
Electronics Enclosure
IP68
Wall Mounted Keypad and Display Dimensions
215mm x 125mm x 90mm (8.46″x 4.92″x 3.54″)