Fluke 1664FC US Installation Multifunction Tester, 500 V, insulation pre-test

Part Number : 1664FC US

Brand :
Fluke

Run seven installation tests automatically in one sequence with a single connection with this installation multifunction tester which features an insulation pre-test to prevent damage to connected appliances. In addition, this tester allows wireless transmission and viewing of test results from the field on a smartphone.

View all

KWD 931.550


Quantity



Description
Specifications
Downloads
Related products

Description

Fluke 1664FC US OffersVerify the safety of electrical installations with this installation multifunction tester capable of ensuring that fixed wiring is safe and correctly installed to meet the requirements of IEC 60364. Additionally, this tester features cloud storage to save your test results and reduce transcription errors.FeaturesMultifunction tester that tests to all local regulationsIncludes insulation pre-test that detects when appliances are connected to the system and stops the testRuns seven installation tests automatically in one sequence with a single connection through auto testAllows you to share test results in real time over your smartphoneView test results on your smartphone via mobile app, download the free app to enable wireless data transmission and storageInsulation pretest; the only installation testers that help prevent damage to connected appliancesAuto test sequence; start a sequence of seven critical tests with one press of the test buttonHeavy duty, single input line cord guards against failures in the fieldReduce test time up to 40% with auto testAuto test does five required installation tests in one sequence, including selectable type A, AC and RCD auto test, ensuring compliance with local installation regulations. It reduces the number of manual connections, decreases the possibility of making errors and reduces test time up to 40% from previous modelsInsulation pretestProtect the installation. Avoid costly mistakes. The installation tester is the only installation with “insulation pretest," which warns you about potentially serious and costly mistakes. If the tester detects that appliances are connected to the system during test, it will stop the insulation test and provide a visual and audible warning. This helps eliminate accidental damage to peripheral equipment and keeps your customers happy.Share from anywhereSave time, eliminate data entry by wirelessly syncing measurements directly from your installation tester and share with your team. Having access to measurements simultaneous at the inspection site and from the office or an off-site location enables faster decision making and real time collaboration between team members.Cloud storageRetrieve stored results from anywhere. Cloud storage allows you to retrieve stored results whether you are in the office or in the field to make decisions in real time. Uses radio-enabled test tools and a mobile app to transfer measurements straight from the field to a secure cloud location, where the data can be accessed by team members. Plus you can import the data into DMS to process and generate certificates.ApplicationsVerify the safety of electrical installations

Downloads

1664FC US.pdf

pdf

Specifications

AC and DC Voltage Measurement Trms
Range: 500 V Resolution: 0.1 V Input impedance: 3.3 MΩ Overload protection: 660 V rms
Continuity Testing (RLO)
Range (autoranging): 20 Ω/200 Ω/2000 Ω Resolution: 0.01 Ω/0.1 Ω/1 Ω Open circuit voltage: >4 V
Insulation Resistance Measurement (RISO)
Test voltages: 50/100/250/500/1000 V Test voltage: 50 V, Insulation resistance range: 20 MΩ/50 MΩ, Test current: 1 mA at 50 kΩ Test voltage: 100 V, Insulation resistance range: 20 MΩ/100 MΩ, Test current: 1 mA at 100 kΩ Test voltage: 250 V, Insulation resistance range: 20 MΩ/200 MΩ, Test current: 1 mA at 250 kΩ Test voltage: 500 V, Insulation resistance range: 20 MΩ/200 MΩ/500 MΩ, Test current: 1 mA at 500 kΩ Test voltage: 1000 V, Insulation resistance range: 20 MΩ/200 MΩ/1000 MΩ, Test current: 1 mA at 1 MΩ
Insulation Safety Pretest
Requires to connect the tester to L, N and PE
Loop and Line Impedance (ZI)
Range: 10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω Resolution: 1 mΩ/ 0.01 Ω/ 0.1 Ω/1Ω
Prospective Earth Fault Current, PSC Test
Range: 1000 A/10 kA (50 kA) Resolution: 1 A/0.1 kA Computation: Prospective earth fault current (PEFC) or prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively
RCD Testing, RCD Types Tested
RCD Type: AC (responds to AC) General, no delay Time delay Responds to pulsed signal Responds to smooth DC signal
RCD Trip Time Test (ΔT)
Current Settings (1000 mA type AC only. 700 mA maximum type A in VAR mode, VAR mode not available for type B) 10/30/100/300/500/1000 mA – VAR 10/30/100 mA Multiplier: x½, x 1 Measurement range RCD type G: 310 ms 50 ms Measurement range RCD type S: 510 ms 160 ms
RCD Trip Current Measurement/Ramp Test (I ΔN)
Current range: 30 to 110% of RCD rated current (30 to 150% for Type A IΔN >10 mA) Step size: 10% of IΔN (5% for Type B) Dwell time type G: 300 ms/step Dwell time type S: 500 ms/step Measurement Accuracy: ±5% Notes: 30 to 210% for Type A IΔN = 10mA, 20 to 210% for Type B Specified trip current ranges (EN 61008-1): 50 to 100% for Type AC 35 to 140% for Type A (>10 mA) 35 to 200% for Type A (≤10 mA) 50 to 20 % for Type B
Earth Resistance Test (RE)
Range: 200 Ω/2000 Ω Resolution: 0.1 Ω/1 Ω Frequency: 128 Hz Output voltage: 25 V
Phase Sequence Indicaton
Icon: Phase sequence indicator is active Range: 100 to 500 V Display: “1-2-3": or “3-2-1"
Performance
EC/EN61557-1 to IEC/EN61557-7 and IEC/EN61557-10
Overvoltage
CAT III 500 V, CAT IV 300 V
Safety
Complies with IEC/EN61010-1, UL61010, ANSI/ISA –s82.02.01 and CAN/CSA c22.2 No. 1010
Sealing
IP 40
Battery
1.5 V type AA (IEC LR6), 6 pcs
Dimensions
3.93 x 9.84 x 4.92" (10 x 25 x 12.5 cm)
Weight
Approximately 2.86 lbs (1.3 kg) including batteries
Industrial Spare Logo

Industrial Spare
Typically replies within an hour

Industrial Spare
Hi there,

How can I help you?
+96566651231
×
Chat with Us