Fluke 1623-2-KIT Offers Simpler, faster earth ground tests than ever before. The tester has internal memory storage with up to 1500 records, accessible via USB port for rapid data transfer and viewing of results. It comes with world-class accessories. New wire reels, speed up setup and tear down time as much as 50%. Heavy duty stakes can be hammered into dry, hard soil. Set up is simpler with new color-coded wires that help eliminate mistakes. Features One-button measurement concept 3- and 4-pole earth ground measurement 4-pole soil resistivity testing Selective testing, no disconnection of ground conductor (one clamp) Stakeless testing, quick ground loop testing (two clamps) Measuring frequency 128 Hz Applications Oil and gasMining/mineral and metal processingProcess manufacturing - chemical processingUtilitiesManufacturing: machinery, instrumentation, and appliances

Downloads

1623-2-KIT.pdf

pdf

Specifications

Operating Temperature
14 to 122°F (-10 to 50°C)
Storage Temperature
-22 to 140°F (-30 to 60°C)
Temperature Coefficient
±0.1% of reading/°C <18°C >28°C
Intrinsic Error
Refers to the reference temperature range and is guaranteed for one year
Operating Error
  • Refers to the operating temperature range and is guaranteed for one year
  • ±(5% rdg + 3 d)
  • ±(10% rdg + 5 d)
Climatic Class
C1 (IEC 654-1), 23 to 115°F (-5 to 45°C), 5 to 95% RH
Protective Type
IP56 for case, IP40 for battery door according to EN60529
Safety
Protection by double and/or reinforced insulation maximum 50 V to earth. IEC61010-1: 300V CAT II, Pollution degree two
EMC (Emission Immunity)
IEC61326-1: Portable
Quality System
Developed, designed, and manufactured according to DIN ISO 9001
External Voltage
V external, maximum = 24 V (dc, ac <400 Hz), measurement inhibited for higher values
V Ext Rejection
>120 dB (16²⁄3, 50, 60, 400 Hz)
Measuring Time
Typical six seconds
Maximum Overload
250 V rms (pertains to misuse)
Auxiliary Power
6 x 1.5 V Alkaline (type AA LR6)
Battery Life Span
Typical >3000 measurements
Switch Position
  • RA 3-pole
  • RA 4-pole
  • RA 3-pole with clamp
  • RA 4-pole with clamp
  • RA 4-pole 2 clamps
Resolution
0.001 to 10 Ω
Measuring range
0.020 Ω to 19.99 kΩ
Accuracy
  • ±(2% rdg + 3 d)
  • ±(7% rdg + 3 d)
Measuring Voltage
Vm = 48 V ac
Short-Circuit Current
>50 mA
Measure Frequency
128 Hz
Probe Resistance (RS)
Maximum 100 kΩ
Auxiliary Earth Electrode Resistance (RH)
Maximum 100 kΩ
Additional Error from RH and RS
RH[kΩ]RS[kΩ]/RA[Ω]0.2%
Probe Resistance (RS + RES)
Maximum 100 kΩ
Noise Current (IEXT)
Maximum IEXT = 10 A (ac) (RA <20 Ω)
Display
1999 Digit LCD: Display with special symbols, digit height 25 mm, fluorescent backlight
User Interface
Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
Robust, Water and Dust Resistant
Instrument is designed for tough environmental conditions (rubber protective cover, IP56)
Memory
Internal memory storage up to 1500 records accessible via USB port
Weight
2.43 lbs (1.1 kg) including batteries 16.8 lbs (7.6 kg) included accessories and batteries in carrying case