Fireye 45UV5 Series Scanner |45UV5-1101EX

45uv5-1101ex.webp

Images may vary slightly

See specifications for accurate information.

Part Number : 45UV5-1101EX

Brand : Honeywell

Fireye Type 45UV5 scanners are self-checking, flame sensing devices. When powered by a compatible, self-checking...

View all

$ 9676


Quantity In Stock



Description
Specifications
Downloads
Related products

Description

Fireye Type 45UV5 scanners are self-checking, flame sensing devices. When powered by a compatible, self-checking Fireye control, the scanners detect the presence or absence of flames which emit ultraviolet radiation (UV). Typical fossil fuels which emit UV include natural gas, propane, methane, butane, kerosene, light petroleum distillates and diesel fuels. For burners firing steam-atomized oil or pulverized coal, Fireye recommends the use of infrared (IR) scanners. Fireye offers a complete line of infrared scanners best suited for these applications. Features: The UV tube, quartz lens, power transformer and related electronic components are contained in an aluminum enclosure which is sealed with high temperature oil-resistant gaskets.  The quartz lens is a planoconvex type which increases the scanner’s sensitivity up to 400 percent. A hinged mount is provided to permit easy access for cleaning the lens.  A double screw-and-keyhole slot arrangement permits quick removal of the housing from its mount.  The scanner has a 1" fitting for mounting to a threaded sight pipe and a 3/8" threaded connection for purge air. Also included in the Type 45UV5 scanner is an electromagnetic shutter that permits a self-checking circuit within an associated Fireye control to verify that the scanner and signal circuits are producing valid flame presence or absence information.  During the shutter closed period the detector’s optical path is blocked from flame radiation.  While the shutter is open, flame presence or absence is detected.  The resultant scanner output, while flame is detected, is a continuous, periodically interrupted pulsed flame signal. This is a prerequisite for energizing the associated Fireye control’s flame relay.

Downloads

45UV5-1101EX_Fireye_45UV5 Series Scanner_Datasheet.pdf

pdf

Specifications

Accuracy
±0.5 mm
Sensor Type
Infrared
Power Supply
24V DC
Interface
Modbus RTU
Temperature (°C)
-20°C to +70°C
Measurement Range
0.1 to 500 mm
Industrial Spare Logo

Industrial Spare
Typically replies within an hour

Industrial Spare
Hi there,

How can I help you?
+96566651231
×
Chat with Us